Mine Power Feeder
Type
MPF-GC Three Conductor
XLP/PVC 8 kV
|
|
| A
P P L I C A T I O N S |
1.
2.
3. |
Primary power
distribution in mines
Used in boreholes, shafts and horizontal runs
High voltage power applications wet or dry |
|
4.
5. |
Aerially
suspended on insulators
Semi-permanent power |
|
| S
P E C I F I C A T I O N S |
1.
2.
3.
4.
5.
|
Conductor:
Stranded soft-drawn uncoated copper
Conductor Shield: Extruded semi-conducting layer
Insulation: Cross-linked polyethylene (XLP)*
Shield: Copper tape over semi-conducting layer
Ground Conductors: Two stranded soft-drawn coated copper
conductors
|
|
6.
7.
8.
9.
10.
11. |
Ground
Check: Stranded coated copper with yellow insulation
Jacket: Polyvinyl chloride (PVC)*
Temperature: 90°C
Voltage: 8000 Volts
Color Code: Chart No. 4 **
Industry Approvals:
MSHA, ICEA, NEMA |
|
Part
No. |
Size
AWG/
MCM |
No.
of
Cond. |
No.
of
Strnd ¤ |
Grnd.
Cond.
Size
AWG |
Grnd
Check
Size
AWG |
Insul.
Thick.
in. |
Jckt.
Thick.
in. |
Approx.
O.D.
inches |
Amp.§
Rate |
Approx.
Weight
lbs/Mft |
| 100%
Insulation Level |
| 08-EE-3403 |
6 |
3 |
7 |
10 |
10 |
.100 |
.110 |
1.31 |
93 |
971 |
| 08-EE-3603 |
4 |
3 |
7 |
8 |
8 |
.080 |
.110 |
1.41 |
122 |
1256 |
| 08-EE-3803 |
2 |
3 |
7 |
6 |
8 |
.080 |
.110 |
1.54 |
159 |
1647 |
| 08-EE-3903 |
1 |
3 |
19 |
5 |
8 |
.080 |
.110 |
1.62 |
184 |
1898 |
| 08-EE-4003 |
1/0 |
3 |
19 |
4 |
8 |
.080 |
.140 |
1.76 |
211 |
2325 |
| 08-EE-4103 |
2/0 |
3 |
19 |
3 |
8 |
.080 |
.140 |
1.86 |
243 |
2716 |
| 08-EE-4203 |
3/0 |
3 |
19 |
2 |
8 |
.080 |
.140 |
1.97 |
279 |
3230 |
| 08-EE-4303 |
4/0 |
3 |
19 |
1 |
8 |
.080 |
.140 |
2.09 |
321 |
3860 |
| 08-EE-4403 |
250 |
3 |
37 |
1/0 |
8 |
.080 |
.140 |
2.21 |
355 |
4460 |
| 08-EE-4803 |
350 |
3 |
37 |
2/0 |
8 |
.080 |
.140 |
2.43 |
435 |
5772 |
| 08-EE-5303 |
500 |
3 |
37 |
4/0 |
8 |
.080 |
.140 |
2.71 |
536 |
7912 |
| 133%
Insulation Level |
| 08-EF-3403 |
6 |
3 |
7 |
10 |
10 |
.080 |
.110 |
1.42 |
93 |
1088 |
| 08-EF-3603 |
4 |
3 |
7 |
8 |
8 |
.080 |
.110 |
1.52 |
122 |
1372 |
| 08-EF-3803 |
2 |
3 |
7 |
6 |
8 |
.080 |
.110 |
1.65 |
159 |
1765 |
| 08-EF-3903 |
1 |
3 |
19 |
5 |
8 |
.080 |
.140 |
1.79 |
184 |
2133 |
| 08-EF-4003 |
1/0 |
3 |
19 |
4 |
8 |
.080 |
.140 |
1.88 |
211 |
2459 |
| 08-EF-4103 |
2/0 |
3 |
19 |
3 |
8 |
.080 |
.140 |
1.97 |
243 |
2866 |
| 08-EF-4203 |
3/0 |
3 |
19 |
2 |
8 |
.080 |
.140 |
2.08 |
279 |
3350 |
| 08-EF-4303 |
4/0 |
3 |
19 |
1 |
8 |
.080 |
.140 |
2.20 |
321 |
4010 |
| 08-EF-4403 |
250 |
3 |
37 |
1/0 |
8 |
.080 |
.140 |
2.32 |
355 |
4653 |
| 08-EF-4803 |
350 |
3 |
37 |
2/0 |
8 |
.080 |
.140 |
2.55 |
435 |
5942 |
| 08-EF-5303 |
500 |
3 |
37 |
4/0 |
8 |
.080 |
.170 |
2.89 |
536 |
8272 |
|
* Available with thermoset insulation and jacket
** Other methods of conductor identification available
¤ Other strand counts available
§ Ampacities per ICEA/NEMA (refer to NEC handbook for National Electrical Code
Ampacities). |
|
|
JCH Wire & Cable... striving to exceed
customer expectations for quality, service, and value