XLP / PVC

Three Conductor Non-Shielded
MV-90 5kV

high voltage cable

high voltage XLP/PVC 5KV
A P P L I C A T I O N S
1.
2.
3.
4.
5.
Raceways
Aerial (when properly supported)
Industrial plants
Primary power and distribution circuits
Utility substations
6.
7.
8.
9.
10.
Generating plants
Wet or dry locations
Conduit, ducts, open tray or free air
Direct burial
Feeders, distribution, and branch circuits
S P E C I F I C A T I O N S
1.
2.

3.
4.
5
6.
Conductors: Stranded soft-drawn bare copper
Conductor Shield: Semi-conducting compound or tape
Insulation: Cross-linked polyethylene (XLP)
Ground Wire: Stranded bare copper**
Cabling: Suitable lay with fillers
Jacket: Sunlight resistant polyvinyl chloride (PVC)
7.

8.

9.
Temperature: 90°C continuous,
130°C emergency, 250°C short circuit
Voltage: 5000 Volts 100% & 133% insulation level
Industry Approvals:
UL 1072 listed type MV-90
ICEA S-66-524
NEMA WC7
Part
Number
Size
AWG/
MCM
No. of
Strands
Ground
Size
AWG
Insul.
Thick.
inches
Jacket
Thick.
inches
Approx.
O.D.
inches
Ampacity*
Rating
Approx.
Weight
lbs/Mft
100% & 133% Insulation
04-FC-3207 8 7 8 .110 .080 1.11 59 583
04-FC-3407 6 7 6 .110 .080 1.19 79 801
04-FC-3607 4 7 6 .110 .080 1.30 105 1031
04-FC-3807 2 7 6 .110 .080 1.44 140 1341
04-FC-3919 1 19 4 .110 .080 1.51 160 1535
04-FC-4019 1/0 19 4 .110 .080 1.60 185 1888
04-FC-4119 2/0 19 4 .110 .080 1.70 215 2100
04-FC-4219 3/0 19 3 .110 .110 1.87 250 2694
04-FC-4319 4/0 19 3 .110 .110 1.99 285 3160
04-FC-4437 250 37 3 .120 .110 2.14 320 3580
04-FC-4637 300 37 2 .120 .110 2.30 355 3758
04-FC-4837 350 37 2 .120 .110 2.37 395 4780
04-FC-5037 400 37 2 .120 .110 2.49 420 5210
04-FC-5337 500 37 1 .120 .110 2.65 485 6320
04-FC-5661 600 61 1 .130 .140 3.00 540 6705
04-FC-6061 750 61 1/0 .130 .140 3.17 615 9225
04-FC-6561 1000 61 1/0 .130 .140 3.44 705 11602
* Amps per conductor is in accordance with NEC table 310-71, for three conductor copper cable isolated  in air, based on a conductor temperature of 90°C and ambient temperature of 40°C. For other installation conditions, refer to the National Electrical Code.