| EPR
/ PVC
Single
Conductor
Shielded AEIC CS-6 MV-90 5kV
|
|
| A
P P L I C A T I O N S |
1.
2.
3.
4.
|
Raceways
Aerially (when properly supported)
Industrial plants
Primary power and distriubtion circuits
|
|
5.
6.
7.
8.
9. |
Utility substations
Generating plants
Wet or dry locations
Conduits, ducts, open tray, or open air
Direct burial |
|
| S
P E C I F I C A T I O N S |
1.
2.
3.
4. |
Conductor:
Stranded soft-drawn bare copper
Conductor Shield: Semi-conducting compound or tape
Insulation: Ethylene propylene rubber (EPR)
Insulation Shield: Semi-conducting insulation screen
with a helically applied copper tape shield
|
|
5.
6.
7.
8. |
Jacket:
Polyvinyl chloride (PVC)
Temperature: 90°C continuous,
130°C emergency, 250°C short circuit
Voltage: 5000 Volts 100% + 133% insulation level
Industry Approvals:
UL 1072 listed MV-90 wet or dry
ICEA S-68-516, NEMA WC8, AEIC CS-6 |
|
Part
Number |
Size
AWG/
MCM** |
No.
of
Strands |
Insul.
Thick.
in |
Jacket
Thick.
in |
Approx.
O.D.
inches |
Ampacity*
Rating |
Approx.
Weight
lbs/Mft |
| 100%
& 133% Insulation Level |
| 04-AH-1332 |
8 |
7 |
.090 |
.060 |
0.60 |
55 |
200 |
| 04-AH-1334 |
6 |
7 |
.090 |
.060 |
0.63 |
75 |
255 |
| 04-AH-1336 |
4 |
7 |
.090 |
.060 |
0.68 |
97 |
321 |
| 04-AH-1338 |
2 |
7 |
.090 |
.060 |
0.74 |
130 |
424 |
| 04-AH-1339 |
1 |
19 |
.090 |
.060 |
0.78 |
155 |
491 |
| 04-AH-1340 |
1/0** |
19 |
.090 |
.060 |
0.81 |
180 |
576 |
| 04-AH-1341 |
2/0** |
19 |
.090 |
.080 |
0.90 |
205 |
680 |
| 04-AH-1342 |
3/0** |
19 |
.090 |
.080 |
0.95 |
240 |
843 |
| 04-AH-1343 |
4/0** |
19 |
.090 |
.080 |
1.01 |
280 |
1006 |
| 04-AH-1344 |
250** |
37 |
.090 |
.080 |
1.05 |
315 |
1152 |
| 04-AH-1346 |
300** |
37 |
.090 |
.080 |
1.12 |
340 |
1332 |
| 04-AH-1348 |
350** |
37 |
.090 |
.080 |
1.16 |
385 |
1511 |
| 04-AH-1350 |
400** |
37 |
.090 |
.080 |
1.27 |
410 |
1726 |
| 04-AH-1353 |
500** |
37 |
.090 |
.080 |
1.32 |
475 |
2102 |
| 04-AH-1356 |
600** |
61 |
.090 |
.080 |
1.42 |
505 |
2459 |
| 04-AH-1360 |
750** |
61 |
.090 |
.080 |
1.52 |
600 |
2979 |
| 04-AH-1365 |
1000** |
61 |
.090 |
.080 |
1.67 |
690 |
3834 |
|
* Amps per conductor is in accordance
with NEC table 310-73, for three conductors in an isolated conduit
in air, based on a conductor temperature of 90°C and ambient temperature
of 40°C. For other installation conditions, refer to the National
Electrical Code.
** Sizes 1/0 and larger may be rated for CT use.
NOTE: May also be available with a Hypalon Jacket. |
|
|
JCH Wire & Cable... striving to exceed
customer expectations for quality, service, and value