EPR / PVC

Single Conductor Shielded
AEIC CS-6 MV-90 15kV

high voltage cable

high voltage EPR/PVC 15KV
A P P L I C A T I O N S
1.
2.
3.
4.
5.
Raceways
Aerial (when properly supported)
Industrial plants
Primary power and distribution circuits
Utility substations
6.
7.
8.
9.
Generating plants
Wet or dry locations
Conduit, ducts, open tray or free air
Direct burial
S P E C I F I C A T I O N S
1.
2.

3.
4.

5.
6.
Conductor: Stranded soft-drawn bare copper
Conductor Shield: Semi-conducting compound or tape
Insulation: Ethylene propylene rubber (EPR)
Insulation Shield: Semi-conducting tape with helically applied copper tape shield
Ground Wire: Stranded bare copper**
Cabling: suitable lay with fillers
7.
8.

9.

10.
Jacket: Polyvinyl chloride (PVC)
Temperature: 90°C continuous,
130°C emergency, 250°C short circuit
Voltage: 15000 Volts, 100% & 133% insulation level
Industry Approvals:
UL 1072 listed type MV-90 Wet and Dry
ICEA S-68-516
NEMA WC8
Part
Number
Size
AWG/
MCM**
No. of
Strands
Insul.
Thick.
in
Jacket
Thick.
in
Approx.
O.D.
inches
Ampa-
city*
Rating
Approx.
Weight
lbs/Mft
100% Insulation Level
04-BG-1338 2 7 .175 .080 0.95 150 600
04-BG-1339 1 19 .175 .080 0.99 170 680
04-BG-1340 1/0** 19 .175 .080 1.03 195 770
04-BG-1341 2/0** 19 .175 .080 1.08 225 890
04-BG-1342 3/0** 19 .175 .080 1.13 260 1030
04-BG-1343 4/0** 19 .175 .080 1.19 295 1220
04-BG-1344 250** 37 .175 .080 1.24 330 1370
04-BG-1348 350** 37 .175 .080 1.37 395 1800
04-BG-1353 500** 37 .175 .080 1.50 480 2350
04-BG-1360 750** 61 .175 .080 1.69 585 3210
04-BG-1365 1000** 61 .175 .110 1.98 675 4210
133% Insulation Level
04-BH-1338 2 7 .220 .080 1.04 150 680
04-BH-1339 1 19 .220 .080 1.08 170 760
04-BH-1340 1/0** 19 .220 .080 1.13 195 860
04-BH-1341 2/0** 19 .220 .080 1.17 225 980
04-BH-1342 3/0** 19 .220 .080 1.22 260 1130
04-BH-1343 4/0** 19 .220 .080 1.30 295 1325
04-BH-1344 250** 37 .220 .080 1.36 330 1490
04-BH-1348 350** 37 .220 .080 1.46 395 1880
04-BH-1353 500** 37 .220 .080 1.59 480 2440
04-BH-1360 750** 61 .220 .110 1.87 585 3460
04-BH-1365 1000** 61 .220 .110 2.04 675 4400
* Amps per conductor is in accordance with NEC table 310-73, for three conductors in an isolated conduit in air, based on a conductor temperature of 90°C and ambient temperature of 40°C. For other installation conditions, refer to the National Electrical Code.
** Sizes 1/0 and larger may be rated for CT use
NOTE: May also be available with a Hypalon Jacket.

 