Building Cable | THHN/THWN

Contact Us


Las Vegas, NV


Phone: (800) 827-1144

Phone: (702) 639-4000

Fax: (702) 639-4001




Reno, NV


Phone: (800) 827-6116

Phone: (775) 850-3000

Fax: (775) 850-3001

THHN / THWN

 

thhn/thwn building wire

thhn/thwn building wire
A P P L I C A T I O N S
1.
2.
3.
Machine tools
Appliances
Raceways
4.
5.
6.
Power control circuits
Relay panels
Lighting circuits
S P E C I F I C A T I O N S
1.

2.
3.
4.
Conductor: Solid or stranded soft-drawn bare copper
Insulation
: Polyvinyl chloride (PVC)
Jacket: Nylon coating
Temperature: 90°C dry, 75°C wet
5.
6.

7.
8.
Voltage: 600 Volts
Industry Standards:
Federal Specification J-C-30A
Industry Approvals: UL Listed
Color Code: Chart No. 1
Part
Number
Size
AWG/
MCM
No. of
Strands
Insul.
Thick
inches
Jacket
Thick
inches
Approx.
O.D.
inches
Amps per Cond.* Approx.
Weight
lbs/Mft
THWN
75°C
THHN
90°C
02-AE-1026 14 Solid .015 .004 .108 20* 25* 16
02-AE-1028 12 Solid .015 .004 .125 25* 30* 24
02-AE-1030 10 Solid .020 .004 .156 35* 40* 38
02-AE-1032 8 Solid .030 .005 .207 50 55 62
02-AE-1426 14 19 .015 .004 .118 20* 25* 17
02-AE-1428 12 19 .015 .004 .137 25* 30* 25
02-AE-1430 10 19 .020 .004 .171 35* 40* 39
02-AE-1432 8 19 .030 .005 .226 50 55 65
02-AE-1434 6 19 .030 .005 .264 65 75 98
02-AE-1436 4 19 .040 .006 .335 85 95 166
02-AE-1437 3 19 .040 .006 .363 100 110 204
02-AE-1438 2 19 .040 .006 .396 115 130 251
02-AE-1339 1 19 .050 .007 .455 130 150 322
02-AE-1340 1/0 19 .050 .007 .496 150 170 397
02-AE-1341 2/0 19 .050 .007 .542 175 195 490
02-AE-1342 3/0 19 .050 .007 .593 200 225 608
02-AE-1343 4/0 19 .050 .007 .651 230 260 754
02-AE-1344 250 37 .060 .008 .726 255 290 901
02-AE-1346 300 37 .060 .008 .781 285 320 1069
02-AE-1348 350 37 .060 .008 .831 310 350 1235
02-AE-1350 400 37 .060 .008 .879 335 380 1401
02-AE-1353 500 37 .060 .008 .965 380 430 1681
02-AE-1356 600 61 .070 .009 1.040 420 475 2007
02-AE-1360 750 61 .070 .009 1.150 475 535 2497
* Amps Per Conductor is in accordance with NEC table 310-16 for not more than three conductors in a raceway, 90°C conductor temperature dry for THHN and 75°C conductor temperature wet or dry for THWN and a 30°C ambient temperature. Over current protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10 AWG copper.

 