EPR / CSPE - USE-2
RHH - RHW


EPR/CSPE Use-2 Building Wire

EPR/CSPE Use-2 Building Wire
A P P L I C A T I O N S
1.
2.
For lighting and power circuits
Switchboards
3.
4.
5.
Raceways and ducts
Direct burial
Cable trays
S P E C I F I C A T I O N S
1.
2
3.
4.
5.
Conductor: Stranded soft-drawn coated copper
Insulation
: Ethylene propylene rubber(EPR)
Jacket: Chlorosulfonated polyethylene (CSPE)
Temperature: 90°C dry or wet
Voltage: 600 Volts
6.
7.
Jacket Color: Black
Industry Approvals:
UL standard 44 & 854
UL VW-1 Vertical flame test
ICEA S-68-516
Federal J-C-30B
IEEE 383
Part
Number
Size
AWG/
MCM*
No. of
Strands
Insul.
Thick
inches
Jacket
Thick
inches
Approx.
O.D.
in.
Amps/
Cond.**
90°C
dry/wet
02-CC-1026 14§ Solid .030 .015 .17 25* / 20*
02-CC-1028 12 Solid .030 .015 .18 30* / 25*
02-CC-1030 10 Solid .030 .015 .20 40* / 35*
02-CC-1032 8 Solid .045 .015 .26 55 / 50
02-CC-1326 14 7 .030 .015 .17 25* / 20*
02-CC-1328 12 7 .030 .015 .19 30* / 25*
02-CC-1330 10 7 .030 .015 .22 40* / 35*
02-CC-1332 8 7 .045 .015 .28 55 / 50
02-CC-1334 6 7 .045 .030 .35 75 / 65
02-CC-1336 4 7 .045 .030 .40 95 / 85
02-CC-1337 3 7 .045 .030 .43 110 / 100
02-CC-1338 2 7 .055 .030 .46 130 / 115
02-CC-1339 1 19 .055 .045 .56 150 / 130
02-CC-1340 1/0 19 .055 .045 .60 170 / 150
02-CC-1341 2/0 19 .055 .045 .64 195 / 175
02-CC-1342 3/0 19 .055 .045 .70 225 / 200
02-CC-1343 4/0 19 .055 .045 .75 260 / 230
02-CC-1344 250 37 .065 .065 .86 290 / 255
02-CC-1346 300 37 .065 .065 .92 320 / 285
02-CC-1348 350 37 .065 .065 .97 360 / 310
02-CC-1350 400 37 .065 .065 1.01 380 / 335
02-CC-1353 500 37 .065 .065 1.10 430 / 380
02-CC-1356 600 61 .080 .065 1.21 475 / 420
02-CC-1359 700 61 .080 .065 1.28 520 / 460
02-CC-1360 750 61 .080 .065 1.31 535 / 475
02-CC-1362 800 61 .080 .065 1.35 555 / 490
02-CC-1365 1000 61 .080 .065 1.47 615 / 545
* Single conductor 1/0 AWG and larger are listed "for CT Use" in accordance with NEC Article 318
** Amperes Per Conductor is in accordance with NEC table 310-16 for not more than three conductors in a raceway as RHH-RHW and not more than three conductors in a raceway or cable in earth is USE and ambient temperature of 30°C. Over current protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10 AWG copper.
§Not rated USE.

 