THW

A P P L I C A T I O N S
1. General purpose lighting
2. Power applications
S P E C I F I C A T I O N S
1.

2.
3.
4.
Conductor: Solid or stranded soft-drawn bare copper
Insulation
: Polyvinyl chloride (PVC)
Temperature: 75°C wet or dry
Voltage: 600 Volts
5.

6.
7.
Industry Standards:
Federal Specification J-C-30A
Industry Approvals: UL Listed
Color Code: Chart No. 1
Part
Number
Size
AWG/
MCM
No. of
Strands
Insulation
Thickness
inches
Approx.
O.D.
inches
Amps
per
Cond.*
Approx.
Weight
lbs/Mft
02-AB-1026 14 Solid .045 .16 20* 22
02-AB-1028 12 Solid .045 .18 25* 31
02-AB-1030 10 Solid .045 .20 35* 45
02-AB-1032 8 Solid .060 .26 45 73
02-AB-1326 14 7 .045 .17 20* 24
02-AB-1328 12 7 .045 .19 25* 33
02-AB-1330 10 7 .045 .21 35* 48
02-AB-1332 8 7 .060 .27 45 77
02-AB-1334 6 7 .060 .31 65 112
02-AB-1336 4 7 .060 .36 85 167
02-AB-1337 3 7 .060 .39 100 205
02-AB-1338 2 7 .060 .42 115 253
02-AB-1339 1 19 .080 .49 130 323
02-AB-1340 1/0 19 .080 .53 150 397
02-AB-1341 2/0 19 .080 .58 175 491
02-AB-1342 3/0 19 .080 .63 200 608
02-AB-1343 4/0 19 .080 .69 230 753
02-AB-1344 250 37 .095 .77 255 900
02-AB-1345 300 37 .095 .82 285 1065
02-AB-1346 350 37 .095 .87 310 1232
02-AB-1350 400 37 .095 .92 335 1391
02-AB-1353 500 37 .095 1.01 380 1722
02-AB-1356 600 61 .110 1.12 420 2088
02-AB-1360 750 61 .110 1.22 475 2576
02-AB-1365 1000 61 .110 1.38 545 3390
* Amps Per Conductors is in accordance with NEC table 310-16 for not more than three conductors in a raceway, 75°C conductor temperature and 30°C ambient temperature in a wet or dry location. Over current protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10 AWG copper.