UF and NMC-B

A P P L I C A T I O N S
1. Underground feeder
2. Branch circuit wiring directly buried in earth
S P E C I F I C A T I O N S
1.

2.
Conductor: Solid or stranded soft-drawn bare copper (solid ground wire only)
Insulation
: Sunlight resistant polyvinyl chloride (PVC) for single conductor wire, polyvinyl chloride (PVC) for 2 and 3 conductor wire
3.


4.

5.
6.
Cabling: Single conductors, or multiple conductors with or without solid bare copper ground wire
Jacket: Sunlight resistant polyvinyl chloride (PVC) (multi-conductor cables only)
Temperature: 60°C wet or dry
Voltage: 600 Volts
Part
Number
Size
AWG
No. of
Strands
Insul.
Thick
inches
Jacket
Thick
inches
Approx.
O.D.
inches
Ampa-
city*
UF 60°C
Approx.
Weight
lbs/Mft
Single Conductor UF
02-FB-1026 14 Solid .060 - .188 15 28
02-FB-1028 12 Solid .060 - .205 20 38
02-FB-1030 10 Solid .060 - .226 30 52
02-FB-1032 8 Solid .080 - .296 40 87
02-FB-1334 6 7 .080 - .352 55 123
02-FB-1336 4 7 .080 - .400 70 183
02-FB-1338 2 7 .080 - .460 95 270
02-FB-1339 1 19 .095 - .532 110 341
02-FB-1340 1/0 19 .095 - .573 125 415
02-FB-1341 2/0 19 .095 - .618 145 508
02-FB-1342 3/0 19 .095 - .670 165 634
02-FB-1343 4/0 19 .095 - .728 195 782
Two Conductor NMC-B
02-FB-1100 14 Solid .030 .030 .210 x .435 15 67
02-FB-1101 12 Solid .030 .030 .220 x .445 20 84
02-FB-1102 10 Solid .030 .030 .240 x .475 30 114
02-FB-1103 8 7 .045 .045 .340 x .700 40 206
02-FB-1104 6 7 .060 .045 .410 x .900 55 326
* Ampacity is in accordance with NEC table 310-16 for not more than three conductors in a raceway for cable buried in earth, based on an ambient temperature of 30°C