Aluminum Interlocked

Armor Power Cable
Three Conductor MV-90 Type MC
XLP/PVC Shielded 5KV/B

A P P L I C A T I O N S
1.
2.
3.
4.
Power and lighting circuits
Feeders
Direct burial
Raceways
5.
6.
7.
8.
9.
Control and signal circuits
Aerially (when supported by a messenger)
Class I and II, Division 2 hazardous locations
Class III Division 1 and 2 hazardous locations
Suitable for use in trays or racks
S P E C I F I C A T I O N S
1.
Conductor: Stranded soft-drawn bare copper
2. Insulation: Cross-linked polyethylene (XLP)
3. Cabling: Insulated conductors are cabled with a ground wire, (fillers where needed) and a binding tape
4. Armor: Aluminum interlocked**
5. Shield: Copper Tape
7.

8.
9.
10.
Jacket: Sunlight and flame resistant yellow polyvinyl chloride (PVC)
Temperature:
90°C
Voltage:
5000 Volts
Industry Approvals:
UL approved for CT use
ICEA 210,000 BTU flame test
IEEE 383 flame test
Part
No.
Size
AWG/
MCM
No. of
Strands
No. of
Cond.
Size
AWG
Copper
Ground
Wire
Insul.
Thick
in.
Jacket
Thick
in.
Approx.
O.D.
inches
Amps.*
40°C
Ambient
Approx.
Weight
lbs/Mft
100% & 133% Insulation Level
05-AE-3203 8 7 3 8 .090 .050 1.28 59 725
05-AE-3403 6 7 3 6 .090 .050 1.36 79 945
05-AE-3603 4 7 3 6 .090 .050 1.51 105 1140
05-AE-3803 2 7 3 6 .090 .060 1.66 140 1500
05-AE-3903 1 19 3 4 .090 .060 1.73 160 1730
05-AE-4003 1/0 19 3 4 .090 .060 1.90 185 2030
05-AE-4103 2/0 19 3 4 .090 .060 1.99 215 2475
05-AE-4203 3/0 19 3 3 .090 .060 2.10 250 2980
05-AE-4303 4/0 19 3 3 .090 .060 2.23 285 3425
05-AE-4403 250 37 3 3 .090 .060 2.32 320 3800
05-AE-4603 300 37 3 2 .090 .075 2.47 355 4450
05-AE-4803 350 37 3 2 .090 .075 2.58 395 5105
05-AE-5003 400 37 3 2 .090 .075 2.67 420 5850
05-AE-5303 500 37 3 1 .090 .075 2.89 485 6865
05-AE-5603 600 61 3 1 .090 .075 3.08 540 7980
05-AE-6003 750 61 3 1/0 .090 .085 3.32 615 9645
* Amps Per Conductor is in accordance with NEC 310-71 and a conductor temperature of 90°C and an ambient temperature of 40°C.
** Galvanized steel armor available upon request.