Aluminum Interlocked

Armor Power Cable
Three Conductor MV-90 Type MC
XLP/PVC Non-Shielded 5kV

A P P L I C A T I O N S
1.
2.
3.
4.
Power and lighting circuits
Feeders
Direct burial
Raceways
5.
6.
7.
8.
9.
Control and signal circuits
Aerially (when supported by a messenger)
Class I and II, Division 2 hazardous locations
Class III Division 1 and 2 hazardous locations
Suitable for use in trays or racks
S P E C I F I C A T I O N S
1.
2.
3.


4.
5.
Conductor: Stranded soft-drawn bare copper
Insulation: Cross-linked polyethylene (XLP)
Cabling: Insulated conductors are cabled with a ground wire, (fillers where needed) and a binding tape
Ground Wire: Stranded bare copper
Armor: Aluminum interlocked**
6.

7.
8.
9.
Jacket: Sunlight and flame resistant yellow polyvinyl chloride (PVC)
Temperature:
90°C
Voltage:
5000 Volts
Industry Approvals:
UL approved for CT use
ICEA 210,000 BTU flame test
IEEE 383 flame test
Part
No.
Size
AWG/
MCM
No. of
Strands
  No. of
Cond.
Ground
Wire
Size
AWG
Insul.
Thick
in.
SW
Thick
in.
Approx.
O.D.
inches
Amps.*
40°C
Ambient
Approx.
Weight
lbs/Mft
100% & 133% Insulation Level
05-AD-3203 8 7 3 8 .110 .050 1.21 59 675
05-AD-3403 6 7 3 6 .110 .050 1.29 79 780
05-AD-3603 4 7 3 6 .110 .050 1.40 105 960
05-AD-3803 2 7 3 6 .110 .050 1.52 140 1270
05-AD-3903 1 19 3 4 .110 .050 1.60 160 1560
05-AD-4003 1/0 19 3 4 .110 .050 1.69 185 1820
05-AD-4103 2/0 19 3 4 .110 .060 1.81 215 2115
05-AD-4203 3/0 19 3 3 .110 .060 1.98 250 2780
05-AD-4303 4/0 19 3 3 .110 .060 2.11 285 3105
05-AD-4403 250 37 3 3 .120 .060 2.20 320 3700
05-AD-4603 300 37 3 2 .120 .060 2.37 355 4220
05-AD-4803 350 37 3 2 .120 .060 2.44 395 4740
05-AD-5003 400 37 3 2 .120 .075 2.56 420 5470
05-AD-5303 500 37 3 1 .120 .075 2.74 485 6515
05-AD-5603 600 61 3 1 .130 .075 2.91 540 7720
05-AD-6003 750 61 3 1/0 .130 .075 3.14 615 9315
* Amps Per Conductor is in accordance with NEC table 310-71 and a conductor temperature of 90°C and an ambient temperature of 40°C.
** Galvanized steel armor available upon request.