| A
P P L I C A T I O N S |
1.
2.
3.
4. |
Power and
lighting circuits
Feeders
Direct burial
Raceways |
|
5.
6.
7.
8.
9. |
Control and
signal circuits
Aerially (when supported by a messenger)
Class I and II, Division 2 hazardous locations
Class III Division 1 and 2 hazardous locations
Suitable for use in trays or racks |
|
| S
P E C I F I C A T I O N S |
1.
2.
3.
4.
5. |
Conductor:
Stranded soft-drawn bare copper
Insulation: Cross-linked polyethylene (XLP)
Cabling: Insulated conductors are cabled with a
ground wire, (fillers where needed) and a binding tape
Ground Wire: Stranded bare copper
Armor: Aluminum interlocked** |
|
6.
7.
8.
9. |
Jacket:
Sunlight and flame resistant polyvinyl chloride (PVC)
Temperature: 90°C dry, 75°C wet
Voltage: 600 Volts
Industry Approvals: UL type MC approved for CT use
IEEE 383 flame test |
|
Part
No. |
Size
AWG/
MCM |
No.
of
Conds. |
Insul.
Thick
inches |
Ground
Wire
Size
AWG |
Jacket
Thick
inches |
Approx.
O.D.
inches |
Amps.*
Dry/Wet
90°C/75°C |
Approx.
Weight
lbs/Mft |
| 05-AA-3203 |
8 |
3 |
.045 |
10 |
.050 |
0.81 |
55/50 |
410 |
| 05-AA-3403 |
6 |
3 |
.045 |
8 |
.050 |
0.88 |
75/65 |
550 |
| 05AA-3603 |
4 |
3 |
.045 |
8 |
.050 |
0.98 |
95/85 |
740 |
| 05-AA-3803 |
2 |
3 |
.045 |
6 |
.050 |
1.17 |
130/115 |
1100 |
| 05-AA-3903 |
1 |
3 |
.055 |
6 |
.050 |
1.30 |
150/130 |
1350 |
| 05-AA-4003 |
1/0 |
3 |
.055 |
6 |
.050 |
1.38 |
170/150 |
1600 |
| 05-AA-4103 |
2/0 |
3 |
.055 |
6 |
.050 |
1.48 |
195/175 |
1900 |
| 05-AA-4203 |
3/0 |
3 |
.055 |
4 |
.050 |
1.59 |
225/200 |
2400 |
| 05-AA-4303 |
4/0 |
3 |
.055 |
4 |
.050 |
1.73 |
260/230 |
2900 |
| 05-AA-4403 |
250 |
3 |
.065 |
4 |
.060 |
1.87 |
290/255 |
3400 |
| 05-AA-4803 |
350 |
3 |
.065 |
3 |
.060 |
2.10 |
350/310 |
4400 |
| 05-AA-5303 |
500 |
3 |
.065 |
2 |
.060 |
2.38 |
430/380 |
6100 |
| 05-AA-6003 |
750 |
3 |
.080 |
1 |
.075 |
2.87 |
535/475 |
8800 |
| 05-AA-6503 |
1000 |
3 |
.080 |
1/0 |
.085 |
3.25 |
615/545 |
11500 |
|