| A
P P L I C A T I O N S |
1.
2.
3. |
Power and
lighting circuits
Feeders
Direct burial |
|
4.
5.
6. |
Raceways
Control and signal circuits
Suitable for use in trays, racks, ladders and troughs |
|
| S
P E C I F I C A T I O N S |
1.
|
Conductor:
Stranded soft-drawn bare copper |
| 2. |
Insulation:
Cross linked polyethylene (XLP) |
| 3. |
Cabling:
Insulated conductors are cabled with a ground conductors
(fillers where needed) and binding tape |
| 4. |
Ground
Wire: Stranded bare copper with .030" cross linked
polyethylene (XLP) insulation |
| 5. |
Armor:
Interlocked aluminum alloy** |
|
6.
7.
8.
9.
10. |
Inner
Jacket: Polyvinyl chloride (PVC)
Outer Jacket: Polyvinyl chloride (PVC)
Temperature: -40°C to 90°C
Voltage: 600 Volts*
Industry Standards:
CSA Standard C22.2
CEC Part 1 |
|
Part
No. |
Size
AWG/
MCM |
No.
of
Conds.* |
Size
AWG
Ground
Wire |
Inner
Jkt.
Thick
in. |
Approximate
Diameter |
Approx.
Weight
lbs/Mft |
Inner
Jkt
in. |
Armor
in. |
Outer
Jkt
In. |
| 05-DA-2602 |
14 |
2 |
14 |
.045 |
.380 |
.580 |
.690 |
194 |
| 05-DA-2603 |
14 |
3 |
14 |
.045 |
.450 |
.650 |
.760 |
233 |
| 05-DA-2604 |
14 |
4 |
14 |
.045 |
.480 |
.660 |
.790 |
259 |
| 05-DA-2605 |
14 |
5 |
14 |
.045 |
.480 |
.680 |
.790 |
278 |
| 05-DA-2606 |
14 |
6 |
14 |
.045 |
.520 |
.720 |
.830 |
309 |
| 05-DA-2607 |
14 |
7 |
14 |
.045 |
.550 |
.750 |
.860 |
336 |
| 05-DA-2608 |
14 |
8 |
14 |
.060 |
.620 |
.820 |
.940 |
389 |
| 05-DA-2609 |
14 |
9 |
14 |
.060 |
.640 |
.840 |
.950 |
411 |
| 05-DA-2610 |
14 |
10 |
14 |
.060 |
.680 |
.880 |
1.000 |
443 |
| 05-DA-2612 |
14 |
12 |
14 |
.060 |
.740 |
.940 |
1.060 |
497 |
| 05-DA-2615 |
14 |
15 |
14 |
.060 |
.770 |
.970 |
1.080 |
559 |
| 05-DA-2620 |
14 |
20 |
14 |
.080 |
.880 |
1.100 |
1.210 |
726 |
| 05-DA-2625 |
14 |
25 |
14 |
.080 |
1.020 |
1.240 |
1.350 |
895 |
| 05-DA-2630 |
14 |
30 |
14 |
.080 |
1.090 |
1.310 |
1.430 |
1013 |
| 05-DA-2650 |
14 |
50 |
14 |
.080 |
1.330 |
1.550 |
1.670 |
1459 |
| 05-DA-2700 |
14 |
100 |
14 |
.080 |
1.800 |
2.050 |
2.190 |
2717 |
|