THHN/THWN-2

Aluminum

   
A P P L I C A T I O N S
1.
2.
3.
Conduit and cable tray
Feeders
Branch Circuits
4.
5.
6.
Commercial
Industrial
CT-Use (1/0 and larger)
S P E C I F I C A T I O N S
1.
2.
3.
4.
Conductor: Compact stranded aluminum alloy
Insulation: PVC/Nylon
Cabling: 90°C wet or dry
Voltage: 600 Volts
5.

6.


7.
Industry Standards:
Federal Specification J-C-30B
Industry Approvals: UL standard 83. Meets or exceeds all applicable ASTM requirements
UL VW-1 (sizes 6-1 AWG)
Color Code: Chart No. 1
Part
Number
Size
AWG/
Kcmil
No. of
Strands
Insul.
Thick
inches
Nominal
diam.
inches
Approx.
Weight
lbs/Mft
31-AA-1334 6 7 .030 .239 38
31-AA-1336 4 7 .040 .305 62
31-AA-1338 2 7 .040 .361 91
31-AA-1339 1 19 .050 .414 108
31-AA-1340 1/0 19 .050 .453 142
31-AA-1341 2/0 19 .050 .496 172
31-AA-1342 3/0 19 .050 .541 210
31-AA-1343 4/0 19 .050 .594 258
31-AA-1344 250 37 .060 .659 310
31-AA-1346 300 37 .060 .710 364
31-AA-1348 350 37 .060 .756 417
31-AA-1350 400 37 .060 .800 470
31-AA-1353 500 37 .060 .877 575
31-AA-1356 600 61 .070 .977 698
31-AA-1359 700 61 .070 1.042 803
31-AA-1360 750 61 .070 1.073 855
31-AA-1365 1000 61 .070 1.227 1116